                                                                                   CHAPTER 8
                                                                        INTERIOR FINISHES
                                                 SECTION 801                                   FLAMESPREAD.Thepropagationofflameoverasurface.
                                                   GENERAL                                     FLAME SPREAD INDEX. A comparative measure,
                         801.1Scope.Provisionsofthischaptershallgoverntheuseof                 expressed as a dimensionless number, derived from visual
                         materials used as interior finishes, trim and decorative materi       measurementsofthespreadofflameversustimeforamaterial
                                                                                         -
                         als.                                                                  tested in accordance with ASTM E 84.
                             801.1.1 Interior finishes. These provisions shall limit the       INTERIORFINISH.Interiorfinishincludesinteriorwalland
                             allowable flame spread and smoke development based on             ceiling finish and interior floor finish.
                             location and occupancy classification.                            INTERIORFLOORFINISH.Theexposedfloorsurfacesof
                                Exceptions:                                                    buildings including coverings applied over a finished floor or
                                   1. Materials having a thickness less than 0.036 inch        stair, including risers.
                                      (0.9mm)applieddirectlytothesurfaceofwallsor              INTERIORWALLANDCEILINGFINISH.Theexposed
                                      ceilings.                                                interior surfaces of buildings, including but not limited to:
                                                                                               fixedormovablewallsandpartitions;toiletroomprivacyparti
                                   2. Exposed portions of structural members comply-                                                                          -
                                      ingwiththerequirementsforbuildingsofTypeIV               tions; columns; ceilings; and interior wainscoting, paneling or
                                      construction in Section 602.4 shall not be subject       other finish applied structurally or for decoration, acoustical
                                      to interior finish requirements.                         correction,surfaceinsulation,structuralfireresistanceorsimi-
                             [F] 801.1.2 Decorative materials and trim. Decorative             lar purposes, but not including trim.
                             materials and trim shall be restricted by combustibility and      SMOKE-DEVELOPED INDEX. A comparative measure,
                             theflamepropagationperformancecriteriaofNFPA701,in                expressed as a dimensionless number, derived from measure-
                             accordance with Section 806.                                      mentsofsmokeobscurationversustimeforamaterialtestedin
                             801.1.3 Applicability. For buildings in flood hazard areas        accordance with ASTM E 84.
                             as established in Section 1612.3, interior finishes, trim and     TRIM.Picturemolds,chairrails, baseboards, handrails, door
                             decorative materials below the design flood elevation shall       andwindowframesandsimilardecorativeorprotectivemate-
                             be flood-damage-resistant materials.                              rials used in fixed applications.
                         801.2 Application. Combustible materials shall be permitted
                         to be used as finish for walls, ceilings, floors and other interior                          SECTION 803
                         surfaces of buildings.                                                             WALL AND CEILING FINISHES
                             801.2.1 Windows. Show windows in the exterior walls of                                                                           -
                             the first story above grade shall be permitted to be of wood      803.1 General.Interior wall and ceiling finishes shall be clas
                             or of unprotected metal framing.                                  sified in accordance with ASTM E 84. Such interior finish
                                                                                               materials shall be grouped in the following classes in accor-
                             801.2.2 Foam plastics. Foam plastics shall not be used as         dance with their flame spread and smoke-developed indexes.
                             interior finish or trim except as provided in Section 2603.9         Class A:Flame spread 0-25; smoke-developed 0-450.
                             or2604.Thissectionshallapplybothtoexposedfoamplas-                   Class B: Flame spread 26-75; smoke-developed 0-450.
                             ticsandtofoamplasticsusedinconjunctionwithatextileor
                             vinyl facing or cover.                                               Class C: Flame spread 76-200; smoke-developed 0-450.
                                                                                                  Exception: Materials, other than textiles, tested in accor-
                                                 SECTION 802                                      dance with Section 803.2.
                                                 DEFINITIONS                                   803.2. Interior wall or ceiling finishes other than textiles.
                         802.1 General. The following words and terms shall, for the           Interiorwallorceilingfinishes,otherthantextiles,shallbeper-
                         purposes of this chapter and as used elsewhere in this code,          mitted to be tested in accordance with NFPA 286. Finishes
                         have the meanings shown herein.                                       testedinaccordancewithNFPA286shallcomplywithSection
                                                                                               803.2.1.
                         EXPANDED VINYL WALL COVERING. Wall covering                              803.2.1 Acceptance criteria. During the 40 kW exposure,
                         consisting of a woven textile backing, an expanded vinyl base            the interior finish shall comply with Item 1. During the 160
                         coat layer and a nonexpanded vinyl skin coat. The expanded               kWexposure, the interior finish shall comply with Item 2.
                         base coat layer is a homogeneous vinyl layer that contains a             During the entire test, the interior finish shall comply with
                         blowing agent. During processing, the blowing agent decom-               Items 3 and 4.
                         poses,causingthislayertoexpandbyformingclosedcells.The
                         totalthicknessofthewallcoveringisapproximately0.055inch                     1. Duringthe40kWexposure,flamesshallnotspreadto
                      ➡to 0.070 inch (1.4 mm to 1.78 mm).                                               the ceiling.
                         2006 VIRGINIA CONSTRUCTION CODE                                                                                                    8-1
             08_Va_Bldg_2006.ps                                                           1
             M:\data\CODES\STATE CODES\Virginia\2006\Construction_Building Code\Final VP\08_Va_Bldg_2006.vp
             Tuesday, May 06, 2008 12:28:40 PM
            Color profile: Generic CMYK printer profile
            Composite  Default screen
                   INTERIOR FINISHES
                         2. During the 160 kW exposure, the interior finish shall             2. Materials where the qualifying tests were made
                            comply with the following:                                           withthematerialsuspendedorfurredoutfromthe
                               2.1. Flame shall not spread to the outer extremity                noncombustible backing.
                                    of the sample on any wall or ceiling.            803.5 Interior finish requirements based on group. Interior
                               2.2. Flashover, as defined in NFPA 286, shall not     wall and ceiling finish shall have a flame spread index not
                                    occur.                                           greater than that specified in Table 803.5 for the group and
                         3. The peak rate of heat release throughout the NFPA        location designated. Interior wall and ceiling finish materials,
                            286 test shall not exceed 800 kW.                        other than textiles, tested in accordance with NFPA 286 and
                                                                                     meetingtheacceptancecriteriaofSection803.2.1,shallbeper-
                         4. The total smoke released throughout the NFPA 286         mittedtobeusedwhereaClassAclassificationinaccordance
                            test shall not exceed 1,000 m2.                          with ASTM E 84 is required.
                   803.3Stability.Interiorfinishmaterialsregulatedbythischap-        803.6 Textiles. Where used as interior wall or ceiling finish
                   ter shall be applied or otherwise fastened in such a manner that  materials, textiles, including materials having woven or
                   such materials will not readily become detached where sub-        nonwoven,napped,tufted,loopedorsimilarsurfaceandcarpet
                   jected to room temperatures of 200°F (93°C) for not less than     and similar textile materials, shall comply with the require-
                   30 minutes.                                                       ments of Section 803.6.1, 803.6.2 or 803.6.3.
                   803.4 Application. Where these materials are applied on              803.6.1 Surface burning characteristic test. Textile wall
                   walls, ceilings or structural elements required to have a            and ceiling coverings shall have a Class A flame spread
                   fire-resistance rating or to be of noncombustible construction,      index in accordance with ASTM E 84 and be protected by
                   they shall comply with the provisions of this section.               automatic sprinklers installed in accordance with Section
                      803.4.1 Direct attachment and furred construction.                903.3.1.1 or 903.3.1.2.
                      Where walls and ceilings are required by any provision in         803.6.2 Room corner test, textiles. Textile wall coverings
                      this code to be of fire-resistance-rated or noncombustible        shall meet the criteria of Section 803.6.2.1 when tested in
                      construction, the interior finish material shall be applied       themannerintendedforuseinaccordancewiththeMethod
                      directly against such construction or to furring strips not       Bprotocol of NFPA 265 using the product-mounting sys-
                      exceeding 1.75 inches (44 mm) applied directly against            tem, including adhesive.
                      suchsurfaces.Theinterveningspacesbetweensuchfurring                  803.6.2.1 Method B test protocol. During the 40 kW
                      strips shall be filled with inorganic or Class A material or         exposure, the interior finish shall comply with Item 1.
                      shall be fireblocked at a maximum of 8 feet (2438 mm) in             During the 150 kW exposure, the interior finish shall
                      any direction in accordance with Section 717.                        comply with Item 2. During the entire test, the interior
                      803.4.2Set-outconstruction.Wherewallsandceilingsare                  finish shall comply with Item 3.
                      required to be of fire-resistance-rated or noncombustible               1. During the 40 kW exposure, flames shall not
                      construction and walls are set out or ceilings are dropped                 spread to the ceiling.
                      distances greater than specified in Section 803.4.1, Class A
                      finish materials shall be used except where interior finish             2. During the 150 kW exposure, the interior finish
                      materialsareprotectedonbothsidesbyanautomaticsprin-                        shall comply with the following:
                      kler system or attached to noncombustible backing or fur-                                                                   -
                      ring strips installed as specified in Section 803.4.1. The                    2.1. Flameshallnotspreadtotheouterextremi
                      hangers and assembly members of such dropped ceilings                              ties of the samplesonthe8-footby12-foot
                      that  are below the main ceiling line shall be of                                  (203 mm by 305 mm) walls.
                      noncombustible materials, except that in Type III and V                       2.2. Flashover,asdescribedinNFPA265,shall
                                                                                -                        not occur.
                      construction, fire-retardant-treated wood shall be permit
                      ted. The construction of each set-out wall shall be of                  3. The total smoke released throughout the NFPA
                      fire-resistance-rated construction as required elsewhere in                265 test shall not exceed 1000 m2.
                      this code.
                      803.4.3 Heavy timber construction. Wall and ceiling fin-          803.6.3 Roomcornertest,ceilingandwallfinish.Textile
                      ishes of all classes as permitted in this chapter that are        wallandceilingcoveringsshallmeetthecriteriaofSection
                      installed directly against the wood decking or planking of        803.2.1whentestedinthemannerintendedforuseinaccor-
                      Type IV construction or to wood furring strips applied            dance with NFPA 286 using the product-mounting system,
                      directly to the wood decking or planking shall be                 including adhesive.
                      fireblocked as specified in Section 803.4.1.                   803.7 Expanded vinyl wall coverings. Expanded vinyl wall
                      803.4.4 Materials. An interior wall or ceiling finish that is  coverings shall comply with the requirements for textile wall
                      not more than 0.25 inch (6.4 mm) thick shall be applied        and ceiling materials and their use shall comply with Section
                      directly against a noncombustible backing.                     803.6.
                         Exceptions:                                                    Exception:Expandedvinylwallorceilingcoveringscom-
                                                                                        plying with Section 803.2 shall not be required to comply
                            1. Class A materials.                                       with Section 803.1 or 803.6.
                   8-2                                                                                        2006 VIRGINIA CONSTRUCTION CODE
            08_Va_Bldg_2006.ps                                                       2
            M:\data\CODES\STATE CODES\Virginia\2006\Construction_Building Code\Final VP\08_Va_Bldg_2006.vp
            Tuesday, May 06, 2008 12:28:40 PM
                       Color profile: Generic CMYK printer profile
                       Composite  Default screen
                                                                                                                                                                                                                                                            INTERIOR FINISHES
                                              803.8 Insulation. Thermal and acoustical insulation shall                                                                                803.9.1.2Fire-resistance-ratedconstruction.Acousti-
                                              comply with Section 719.                                                                                                                 cal ceiling systems that are part of fire-resistance-rated
                                                                                                                                                                                       construction shall be installed in the same manner used
                                              803.9Acousticalceilingsystems.Thequality,design,fabrica
                                                                                                                                                                 -                     in the assembly tested and shall comply with the provi
                                                                                                                                                                                                                                                                                               -
                                              tion and erection of metal suspension systems for acoustical                                                                             sions of Chapter 7.
                                              tile and lay-in panel ceilings in buildings or structures shall
                                              conformwithgenerallyacceptedengineeringpractice,thepro
                                                                                                                                                                 -
                                              visionsofthischapterandotherapplicablerequirementsofthis                                                                                                                 SECTION 804
                                              code.                                                                                                                                                       INTERIOR FLOOR FINISH
                                                    803.9.1 Materials and installation. Acoustical materials                                                                804.1General.Interiorfloorfinishandfloorcoveringmateri-
                                                    complying with the interior finish requirements of Section                                                              als shall comply with Sections 804.2 through 804.4.1.
                                                    803shallbeinstalledinaccordancewiththemanufacturer’s                                                                          Exception: Floor finishes and coverings of a traditional
                                                    recommendations and applicable provisions for applying                                                                        type,suchaswood,vinyl,linoleumorterrazzo,andresilient
                                                    interior finish.                                                                                                              floor covering materials that are not comprised of fibers.
                                                         803.9.1.1 Suspended acoustical ceilings. Suspended                                                                 804.2 Classification. Interior floor finish and floor covering
                                                         acoustical ceiling systems shall be installed in accor-                                                            materials required by Section 804.4.1 to be of Class I or II
                                                         dancewiththeprovisionsofASTMC635andASTMC                                                                           materialsshallbeclassifiedinaccordancewithNFPA253.The
                                                                                                                                                                            classification referred to herein corresponds to the classifica
                                                         636.                                                                                                                                                                                                                                  -
                                                                                                                                                            TABLE 803.5
                                                                                                     INTERIOR WALL AND CEILING FINISH REQUIREMENTS BYOCCUPANCYk
                                                                                                                                                l
                                                                                                                        SPRINKLERED                                                                                          NONSPRINKLERED
                                                                                  Exit enclosures and                                                         Rooms and                   Exit enclosures and                                                         Rooms and
                                                                                                              a,b                                                                   c                                 a,b                                                                   c
                                                         GROUP                    exit passageways                           Corridors                   enclosed spaces                  exit passageways                           Corridors                   enclosed spaces
                                                                                                                                                                                                                                             d                                  e
                                                      A-1 & A-2                                  B                                 B                                  C                                 A                                 A                                  B
                                                          f                                                                                                                                                                                  d
                                                   A-3, A-4, A-5                                 B                                 B                                  C                                 A                                 A                                   C
                                                B, E, M, R-1, R-4                                B                                 C                                  C                                 A                                  B                                  C
                                                              FCCCBCC
                                                                                                                                                                        g
                                                              HBBCAAB
                                                             I-1                                 B                                 C                                  C                                 A                                  B                                  B
                                                                                                                                                                       h, i                             AAB
                                                             I-2                                 B                                 B                                B
                                                                                                                                      j
                                                             I-3                                A                                  A                                  CAAB
                                                                                                                                                                       h, i
                                                             I-4                                 B                                 B                                B                                   AAB
                                                            R-2CCCBBC
                                                            R-3CCCCCC
                                                              SCCCBBC
                                                              U                                                         No restrictions                                                                                         No restrictions
                                                                                                                               2
                                              For SI:       1 inch = 25.4 mm, 1 square foot = 0.0929m .
                                              a. ClassCinteriorfinishmaterialsshallbepermittedforwainscottingorpanelingofnotmorethan1,000squarefeetofappliedsurfaceareainthegradelobbywhere
                                                  applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.4.1.
                                                                                                                                                                                                                                                                                               -
                                              b. InexitenclosuresofbuildingslessthanthreestoriesinheightofotherthanGroupI-3,ClassBinteriorfinishfornonsprinkleredbuildingsandClassCinteriorfin
                                                  ish for sprinklered buildings shall be permitted.
                                              c. Requirementsforroomsandenclosedspacesshallbebaseduponspacesenclosedbypartitions.Whereafire-resistanceratingisrequiredforstructuralelements,
                                                  the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered enclosing spaces and the rooms or
                                                  spacesonbothsidesshallbeconsideredone.Indeterminingtheapplicablerequirementsforroomsandenclosedspaces,thespecificoccupancythereofshallbethe
                                                  governing factor regardless of the group classification of the building or structure.
                                              d. Lobbyareas in Group A-1, A-2 and A-3 occupancies shall not be less than Class B materials.
                                              e. Class C interior finish materials shall be permitted in places of assembly with an occupant load of 300 persons or less.
                                              f. For places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be permitted.
                                              g. Class B material is required where the building exceeds two stories.
                                              h. Class C interior finish materials shall be permitted in administrative spaces.
                                              i.  Class C interior finish materials shall be permitted in rooms with a capacity of four persons or less.
                                              j.  Class B materials shall be permitted as wainscotting extending not more than 48 inches above the finished floor in corridors.
                                              k. Finish materials as provided for in other sections of this code.
                                                                                                                                                                                                                                                                                               -
                                              l.  Applieswhentheexitenclosures,exitpassageways,corridorsorroomsandenclosedspacesareprotectedbyasprinklersysteminstalledinaccordancewithSec
                                                  tion 903.3.1.1 or 903.3.1.2.
                                              2006 VIRGINIA CONSTRUCTION CODE                                                                                                                                                                                                              8-3
                       08_Va_Bldg_2006.ps                                                                                                                         3
                       M:\data\CODES\STATE CODES\Virginia\2006\Construction_Building Code\Final VP\08_Va_Bldg_2006.vp
                       Tuesday, May 06, 2008 12:28:41 PM
            Color profile: Generic CMYK printer profile
            Composite  Default screen
                    INTERIOR FINISHES
                    tions determined by NFPA 253 as follows: Class I, 0.45                805.1.3 Insulating boards. Combustible insulating boards
                             2                                  2                                        1
                    watts/cm or greater; Class II, 0.22 watts/cm or greater.              not more than / inch (12.7 mm) thick and covered with
                                                                                                           2
                    804.3 Testing and identification. Interior floor finish and           approved finish flooring are permitted where attached
                    floor covering materials shall be tested by an approved agency        directly to a noncombustible floor assembly or to wood
                    in accordance with NFPA 253 and identified by a hang tag or           subflooring attached to sleepers as provided for in Section
                    othersuitablemethodsoastoidentifythemanufacturerorsup-                805.1.1.
                    plier and style, and shall indicate the interior floor finish or
                    floor covering classification according to Section 804.2. Car
                                                                                 -                          [F] SECTION 806
                    pet-type floor coverings shall be tested as proposed for use,               DECORATIVE MATERIALS AND TRIM
                    including underlayment. Test reports confirming the informa-       [F]806.1Generalrequirements.InoccupanciesinGroupsA,
                    tionprovidedinthemanufacturer’sproductidentificationshall          E,IandR-1anddormitoriesinGroupR-2,curtains,draperies,
                    be furnished to the building official upon request.                hangingsandotherdecorativematerialssuspendedfromwalls
                    804.4 Interior floor finish requirements. In all occupancies,      orceilingsshallmeettheflamepropagationperformancecrite
                                                                                                                                                    -
                    interior floor finish and floor covering materials in exit enclo-  ria of NFPA 701 in accordance with Section 806.2 or be
                    sures,exitpassageways,corridorsandroomsorspacesnotsep-             noncombustible.
                    arated from corridors by full-height partitions extending from        InGroupsI-1andI-2,combustibledecorativematerialsshall
                    the floor to the underside of the ceiling shall withstand a mini-  meet the flame propagation criteria of NFPA 701 unless the
                    mum critical radiant flux as specified in Section 804.4.1.         decorativematerials,including,butnotlimitedto,photographs
                       804.4.1 Minimumcriticalradiant flux. Interior floor fin-        andpaintings,areofsuchlimitedquantitiesthatahazardoffire
                                                                                       development or spread is not present. In Group I-3, combusti
                       ish and floor covering materialsin exit enclosures, exit pas-                                                                -
                       sageways and corridors shall not be less than Class I in        ble decorative materials are prohibited.
                       GroupsI-2andI-3andnotlessthanClassIIinGroupsA,B,                   Fixed or movable walls and partitions, paneling, wall pads
                       E, H, I-4, M, R-1, R-2 and S. In all areas, floor covering      andcrashpadsappliedstructurallyorfordecoration,acoustical
                       materialsshallcomplywiththeDOCFF-1“pilltest”(CPSC               correction,surfaceinsulationorotherpurposesshallbeconsid-
                       16 CFR, Part 1630).                                             ered interior finish if they cover 10 percent or more of the wall
                          Exception: Where a building is equipped throughout           or of the ceiling area, and shall not be considered decorative
                          with an automatic sprinkler system in accordance with        materials or furnishings.
                          Section 903.3.1.1 or 903.3.1.2, Class II materials are          In Group BandMoccupancies,fabricpartitionssuspended
                          permitted in any area where Class I materials are            from the ceiling and not supported by the floor shall meet the
                          required, and materials complying with the DOC FF-1          flame propagation performance criteria in accordance with
                          “pill test” (CPSC 16 CFR, Part 1630) are permitted in        Section 806.2 and NFPA 701 or shall be noncombustible.
                          any area where Class II materials are required.                 [F] 806.1.1 Noncombustible materials. The permissible
                                                                                          amountofnoncombustibledecorative material shall not be
                                           SECTION 805                                    limited.
                       COMBUSTIBLE MATERIALS IN TYPES I AND II                            [F] 806.1.2 Combustible decorative materials. The per-
                                         CONSTRUCTION                                     missible amount of decorative materials meeting the flame
                                                                                          propagation performance criteria of NFPA 701 shall not
                    805.1 Application. Combustible materials installed on or                                                                        -
                                                                                          exceed 10 percent of the aggregate area of walls and ceil
                    embedded in floors of buildings of Type I or II construction          ings.
                    shall comply with Sections 805.1.1 through 805.1.3.                      Exceptions:
                       Exception:Stagesandplatformsconstructedinaccordance                      1. In auditoriums in Group A, the permissible
                       with Sections 410.3 and 410.4, respectively.                                amount of decorative material meeting the flame
                       805.1.1 Subfloor construction. Floor sleepers, bucks and                    propagation performance criteria of NFPA 701
                                                                                 -                 shallnotexceed50percentoftheaggregateareaof
                       nailingblocksshallnotbeconstructedofcombustiblemate                         walls and ceiling where the building is equipped
                       rials, unless the space between the fire-resistance-rated
                       floor construction and the flooring is either solidly filled                throughout with an automatic sprinkler system in
                       with approved noncombustible materials or fireblocked in                    accordance with Section 903.3.1.1 and where the
                       accordance with Section 717, and provided that such open                    material is installed in accordance with Section
                                                                                 -                 803.4.
                       spaces shall not extend under or through permanent parti
                       tions or walls.                                                          2. The amount of fabric partitions suspended from
                       805.1.2 Woodfinishflooring.Woodfinishflooring isper-                        theceilingandnotsupportedbythefloorinGroup
                       mitted to be attached directly to the embedded or                           B and M occupancies shall not be limited.
                       fireblocked wood sleepers and shall be permitted where          [F] 806.2 Acceptance criteria and reports. Where required
                                                                                 -
                       cemented directly to the top surface of approved fire-resis     by Section 806.1, decorative materials shall be tested by an
                       tance-ratedfloorconstructionordirectlytoawoodsubfloor           approvedagencyandmeettheflamepropagationperformance
                       attached to sleepers as provided for in Section 805.1.1.        criteria of NFPA 701 or such materials shall be
                    8-4                                                                                         2006 VIRGINIA CONSTRUCTION CODE
            08_Va_Bldg_2006.ps                                                         4
            M:\data\CODES\STATE CODES\Virginia\2006\Construction_Building Code\Final VP\08_Va_Bldg_2006.vp
            Tuesday, May 06, 2008 12:28:42 PM
The words contained in this file might help you see if this file matches what you are looking for:

...Color profile generic cmyk printer composite default screen chapter interior finishes section flamespread thepropagationofflameoverasurface general flame spread index a comparative measure scope provisionsofthischaptershallgoverntheuseof expressed as dimensionless number derived from visual materials used trim and decorative materi measurementsofthespreadofflameversustimeforamaterial als tested in accordance with astm e these provisions shall limit the interiorfinish interiorfinishincludesinteriorwalland allowable smoke development based on ceiling finish floor location occupancy classification interiorfloorfinish theexposedfloorsurfacesof exceptions buildings including coverings applied over finished or having thickness less than inch stair risers mm applieddirectlytothesurfaceofwallsor interiorwallandceilingfinish theexposed ceilings surfaces of but not limited to fixedormovablewallsandpartitions toiletroomprivacyparti exposed portions structural members comply ingwiththerequirements...

no reviews yet
Please Login to review.